Skip to Content

EVOHFLEX RIS RAS PIPE

EVOHFLEX RIS RAS Pipe

PERT-II Pipe

5 layers

Reduces oxygen permeability

Full protection

FOR SELF-ADHESIVE SYSTEMS



+ PRODUCT INFORMATION


EVOHFLEX RIS RAS PIPE (5 LAYERS)


Polytherm EVOHFLEX PRO/PLUS anti-diffusion PERT-II pipe with adhesive outer wrapping.

Certified according to UNE EN ISO 22391 standard.

It incorporates an outer polymer coating with metallic microparticles to prevent moisture from coming into contact with the EVOH layer, which:

​o Reduces oxygen permeability.

​o Decreases corrosion.

​o Improves thermal performance.

​o Protects against abrasion during installation.

​o Facilitates installation.


Want to learn more about the underfloor heating System?

Underfloor heating webinar for New Construction

Here we explain all underfloor heating systems for new construction projects!

In the following YouTube video, we show you step by step all the systems for your new construction installations.

​

You can also download the Price List.

Do you have questions?


If you need more information or personalized assistance, feel free to contact us. Estamos aquí para ayudarte.​

To stay up to date, subscribe to our YouTube channel. You’ll receive the latest updates, tutorials, and news about our products.

View more underfloor heating products



Modelos disponibles y referencias de pedido

Consulte a continuación los diámetros y series de la tubería POLYTHERM EVOHFLEX RIS-RAS (Ref: PSRTPERT02):

Diámetro del tubo Campo de trabajo (UNE EN 22391)
Ø 15 x 1,5 mm Serie 4,4 Clase 5 PN15
Ø 16 x 1,8 mm Serie 4 Clase 5 PN15

Especificaciones y Datos Técnicos

Norma de certificación UNE EN ISO 22391 (Certificado AENOR Nº 001/0006330)
Campo de aplicación Instalaciones de climatización y calefacción
Valor de rugosidad 0,007 mm
Conductividad térmica 0,35 W/K·m
Coeficiente lineal de dilatación 0,15 mm/m·K
Rango de Tª de trabajo -20 °C a +90 °C
Radio de curvatura 5 x D
Resistencia a la tracción 18 N/mm² (DIN 53455)
Elongación a la rotura 380% (DIN 53455)
Módulo E 500 MPa (DIN 53457)